Transformers convert AC voltage by electromagnetic induction.Specifically, transformers convert high voltage from power plants and substations, etc. to a voltage that is suitable for respective purposes and applications.

Features

We manufacture built-to-order products. We propose optimal equipment to customers to meet various requirements such as installation restrictions, low noise, and high efficiency. For oil filled transformers, various options are available to prevent oil deterioration, including the OF type, conservator type (diaphragm type and rubber cell type), and nitrogen-sealed type.

Rating

Oil Filled Transformerwith De-Energized Tap Changer(DETC)

Model Outdoor oil filled self-cooled type
Phases 3-phase
Frequency 50/60Hz
Primary Voltage 22kV 33kV 66kV 77kV
Second Voltage 3.3/6.6kV 6.6kV
Capacity 1,000~10,000kVA 1,000~40,000kVA
Connection Y-△(Yd1) △-△(Dd0) Y-△(Yd1)
Tap Voltage F23-R22-F21-F20 F34.5-R33-F31.5-F30 F69-R66-F63-F60 F80.5-R77-F73.5-F70

Nitrogen-filled Transformerwith DETC

Model Outdoor oil filled self-cooled type
Phases 3-phase
Frequency 50/60Hz
Primary Voltage 22kV 33kV 66kV 77kV
Second Voltage 3.3/6.6kV 6.6kV
Capacity 1,000~10,000kVA 1,000~40,000kVA
Connection Y-△(Yd1) △-△(Dd0) Y-△(Yd1)
Tap Voltage F23-R22-F21-F20 F34.5-R33-F31.5-F30 F69-R66-F63-F60 F80.5-R77-F73.5-F70

Oil Filled Transformerwith On-Load Tap Changer(OLTC)

Model Outdoor oil filled self-cooled type
Phases 3-phase
Frequency 50/60Hz
Primary Voltage 66/77kV
Capacity 3,000~20,000kVA
Tap Voltage F69~R64.5~F60(17点)
F80.5~R75.25~F70(17点)

SF6 gas insulated transformerwith DETC

Model Outdoor oil filled self-cooled type
Phases 3-phase
Frequency 50/60Hz
Primary Voltage 22kV 33kV 66kV 77kV
Second Voltage 3.3/6.6kV 6.6kV
Capacity 1,000~10,000kVA 1,000~15,000kVA
Connection △-△(Dd0) Y-△(Yd1)
Tap Voltage F23-R22-F21-F20 F34.5-R33-F31.5-F30 F69-R66-F63-F60 F80.5-R77-F73.5-F70